Please use this identifier to cite or link to this item: http://studentrepo.iium.edu.my/handle/123456789/2631
Title: Earth-to-air heat exchanger system simulation study for IIUM Gombak
Authors: Ahmed, Soran Hama Aziz
Subject: Air conditioning
Buildings -- Energy conservation
Buildings -- Environmental engineering
Year: 2013
Publisher: Kuala Lumpur: International Islamic University Malaysia, 2013
Abstract in English: This study elucidates the usage of the Earth-to-Air Heat Exchanger (EAHE) system. The emphasis is on replacing the conventional air conditioning systems with the EAHE technology, as low energy cooling system for residential and commercial buildings in Malaysia. The turnover in the usage will contribute to reducing electric-energy consumption and minimize environmental impact caused by the high usage of electrical appliances for cooling in the buildings. The EAHE technology uses simple methods of transferring the air from its intake into the ground through a pipe, and it releases the air from its outlet into a building or a room. The air travels through the pipe and gives away some heat to the surrounding underground soil, and then enters into the room as cool air. To fulfill the requirements of the empirical investigations, this research utilized the EnergyPlus program to simulate the EAHE system, based on ASHRAE weather database and data collected in previous field studies at the IIUM Gombak Campus, Kuala Lumpur, Malaysia. This study went through some meta-analysis and observations on the cooling potential (ΔT) which represents the difference between ambient air temperature (Tam) and pipe outlet air temperature (Tpo). The research also observed the influence of other factors such as pipe diameter, air velocity, pipe-depth, and pipe-length on the cooling potential (ΔT). The simulation results showed that, the maximum (ΔT) achieved by utilizing the EAHE was 3.57 °C at 2:00 pm. The PVC pipe is required to achieve the aforementioned reduction of 0.075 m (3 inches) in diameter, 50 m long, and placed 1.0 m deep underground, with an air velocity of 1 m.s-1.
Degree Level: Master
Call Number: t TH 7687.5 A2867E 2013
Kullliyah: Kulliyyah of Architecture and Environmental Design
Programme: Masters of Science in Building Services Engineering
URI: http://studentrepo.iium.edu.my/jspui/handle/123456789/2631
URL: https://lib.iium.edu.my/mom/services/mom/document/getFile/5l7HM7rljOFby3LDm7i3dKGPf6Js5NO420140721093406725
Appears in Collections:KAED Thesis

Files in This Item:
File Description SizeFormat 
t00011294093SoranHama_SEC_24.pdf24 pages file1.14 MBAdobe PDFView/Open
t00011294093SoranHama_SEC.pdf
  Restricted Access
Full text secured file3.18 MBAdobe PDFView/Open    Request a copy
Show full item record

Page view(s)

10
checked on May 18, 2021

Download(s)

4
checked on May 18, 2021

Google ScholarTM

Check